The causes and prevention measures of condensate water generation in cleanroom air conditioning systems
2026/11/10
01 Common Causes
02 Key Points for Prevention and Handling
1. Control the moisture load first
During summer and high-humidity seasons, the new air dehumidification capacity should be carefully verified. In necessary cases, new air pre-treatment, secondary air cooling, or independent dehumidification should be adopted. The relative humidity in the clean area is generally recommended to be controlled within the upper limit of the process verification, with common requirements being A/B/C grades ≤ 60% and D grades ≤ 65%.
2. Maintain a micro-positive pressure in the clean area
Avoid negative pressure drawing in hot and humid air into the negative pressure section of the air conditioning system or the technical interlayer. Between different functional areas of the same cleanliness level and between the clean area and non-clean areas, a specified pressure gradient should be maintained.
3. Inspect the heat exchangers and filters
Dust accumulation, oil stains, or tilting of the fins of the heat exchanger will reduce the heat exchange efficiency, leading to increased local undercooling and condensation; the increase in resistance of the primary and intermediate efficiency filters will also reduce the air volume and affect the dehumidification effect. During the rainy season, the inspection frequency can be appropriately increased.
4. Check the condensate water drainage system
The horizontal section of the condensate water pipe should maintain a continuous downhill slope, usually not less than 1%; the capacity of the water collection pan should be reserved with sufficient margin; the height of the water seal in the trap should be able to overcome the negative pressure of the air conditioning box to avoid water seal being drained dry and poor drainage or odor backflow.
5. Strengthen insulation and eliminate cold bridges
All contact points of the chilled water pipe, condensate water pipe, ductwork, valves, flanges, and supports should be inspected for continuous insulation. Insulation damage, insufficient thickness, or unsealed joints can easily cause secondary condensation.
6. Optimize operation strategies
Do not reduce the fan speed to the point that it affects the pressure difference and ventilation. In the BMS, humidity compensation, dew point monitoring, and minimum operating frequency locking can be added; before resuming production, it is necessary to confirm that the temperature, humidity, pressure difference, particles, and microorganisms are stable.
7. When there is overflow, isolate first and then investigate
Immediately stop the supply air to the affected area or switch to a safe mode to prevent the spread of contamination; clear the drainage pipe, clean the water collection pan and disinfect it; recheck the slope, water seal, insulation, and the operating conditions of the heat exchanger; if necessary, install a leak detection rope or liquid level alarm.
8. On-site rapid inspection checklist
Check the supply and return air dampers/temperature of the dew point: determine if the dehumidification is truly insufficient. Check the pressure difference and door and window sealing: eliminate the infiltration of hot and humid air. Check the pressure difference of the filters: confirm if the air volume has decayed. Check the temperature difference between the supply and return water of the heat exchanger and the valve opening: determine if the heat exchange is normal. Check the liquid level of the water collection pan, the slope of the drainage pipe, and the water seal to see if there is water. Check the insulation of the ductwork, water pipes, valves, and if it is continuous. Check the filter screen of the new air inlet and rain protection measures, especially during the rainy season. High humidity in electronic cleanrooms not only causes condensation but may also bring corrosion, dust adhesion, and static control problems; if it involves secondary distribution, color steel plate ceilings, or air shower areas, it is necessary to pay special attention to the wall penetration pipe openings, concealed pipe sections in the ceiling, and inspection ports of the water collection pan. These places are most prone to being overlooked.