Ventilation and makeup air design for clean laboratories

2026/11/10

The ventilation and makeup air design of a clean laboratory is more complex than that of an ordinary laboratory: it needs to not only meet the requirements for personnel protection and negative pressure control, but also take into account the cleanliness level, pressure gradient, filtration system, and HVAC air volume balance.
If there are fume hoods, biosafety cabinets, clean air conditioning systems, high-efficiency filters, color steel plate enclosures, and secondary distribution pipelines in the room, it is recommended to calculate them together based on "exhaust equipment list + cleanliness level + pressure gradient + room volume + HVAC system form".
1. Determine the room attributes
The pressure difference between the clean area and the non-clean area should generally not be less than 5 Pa; the pressure difference between the clean area and the outside or the atmospheric side should typically be no less than 10 Pa.
If it is a toxic, harmful, or biological contamination risk area, it should maintain a slight negative pressure or a graded negative pressure under the premise of meeting the cleanliness requirements.
2. Calculation of exhaust volume
The exhaust volume of a clean laboratory is usually taken as the maximum value of three types:
1. Local exhaust equipment
Fume hoods: calculated by the cabinet area × air velocity, the common air velocity is around 0.5 m/s.
Biosafety cabinets, universal hoods, atomic absorption hoods, reagent cabinets exhaust, accident exhaust, etc. should be counted separately. Biosafety cabinets, highly toxic, strongly corrosive, radioactive, and highly odorous exhaust should be in an independent system.
2. Minimum air change rate of the room
General chemical/ clean laboratory: usually no less than 8-12 times/h. High-risk chemical, organic synthesis, gas chamber: can be taken as 15-20 times/h.
Biological safety, PCR, microbiology: usually ≥ 12 times/h or higher, determined according to the grade.
When the cleanliness level is high, it is also necessary to meet the requirements of clean room air change rate or cross-sectional wind speed.
3. Fresh air volume for personnel
It is usually calculated at 30-40 m³/h per person, and compared with the exhaust balance result to take the larger value.
The final exhaust volume should simultaneously meet: equipment capture + clean air change + personnel fresh air + heat and humidity load + accident exhaust verification.
3. Makeup air volume and pressure difference air volume
The makeup air volume cannot be simply estimated by a fixed proportion. First, do a wind volume balance: makeup air volume = exhaust volume - the air volume required to maintain the pressure difference.
In the initial calculation of the project, the makeup air volume can be taken as 70%-80% of the exhaust volume, and the remaining 20%-30% is used to maintain the negative pressure or pressure gradient of the room.
However, in a clean laboratory, the pressure difference air volume is recommended to be verified using the gap method or air change rate method:
Pressure difference 5 Pa: the pressure difference air volume can be estimated as 1-2 times/h;
Pressure difference 10 Pa: the pressure difference air volume can be estimated as 2-4 times/h.
If the enclosure structure of the clean room has good airtightness, such as color steel plate + sealed door + transfer window, the pressure difference air volume can be taken as the lower limit;
If there are many gaps, frequent opening, and average airtightness, it is recommended to take the upper limit and reserve a debugging margin.
4. Selection of makeup air method
Clean laboratories usually do not recommend relying solely on natural makeup air through gaps. The makeup air should be filtered and heated in cold regions in winter to avoid condensation, cold air direct blowing, and pressure difference fluctuations.
5. Air flow organization and air outlet layout
The clean area should adopt an upward supply and downward exhaust form or an air flow form that meets the cleanliness level requirements.
The supply air outlet should be away from the operation surface of fume hoods and biosafety cabinets to avoid interfering with the surface air velocity.
When the pollutant is heavier than air, an additional lower exhaust outlet should be added.
The intake air outlet should be located in a cleaner outdoor area, and the intake and exhaust air outlets should avoid short circuits; when at the same height, the horizontal distance should be no less than 10m, and the lower edge of the intake air outlet should be no less than 2m from the outdoor ground.
6. Design of pressure gradient
It is recommended to establish a stable gradient according to the process and cleanliness level: clean area → buffer/corridor → general experimental area → high-risk area.
The clean area can maintain +5 Pa;
Generally, the pressure difference in a chemical clean laboratory relative to the corridor is -5 to -10 Pa;
For biosafety or high-risk areas, it can be further reduced to -10 to -30 Pa;
The pressure difference between adjacent areas should be no less than 5 to 10 Pa to prevent backflow when doors are opened or equipment is started or stopped.
VAV variable air volume + pressure feedback control is recommended for clean laboratories:
When the sliding door of the fume hood changes, the exhaust valve responds quickly to maintain a stable face wind speed;
The supply/return air valves follow the changes in exhaust air;
The pressure sensor corrects the difference between supply and exhaust air, maintaining the set pressure difference;
The start/stop of the fan should be interlocked: first open the exhaust, then open the supply; first close the supply, then close the exhaust;
During periods, alternate with on-duty ventilation, but it should not be lower than the minimum ventilation frequency required by the specification.
Eight, connection with HVAC commissioning, secondary distribution, and color steel plate installation
If the project involves HVAC commissioning of the clean workshop, the following points should be carefully checked:
The airtightness of the color steel plate enclosure, doors, transfer windows, directly affects the pressure difference and air volume;
Whether the secondary distribution pipelines, air outlets, inspection ports damage the enclosure seal;
The wind volume attenuation and resistance change after the installation of the high-efficiency filter;
Whether the actual adjustable range of the supply, exhaust, and return air valves covers the maximum/minimum operating conditions;
The pressure recovery speed during door opening, personnel entry/exit, and fume hood start/stop.
Nine, key points for commissioning and acceptance
Check the face wind speed, uniformity, and alarm function of the fume hood;
Verify the air exchange frequency of the room, supply air volume, exhaust air volume, makeup air volume;
Record the pressure difference after stabilization, with the error controlled within a small range;
Perform an opening disturbance test to observe whether the pressure difference recovers quickly;
Check the interlock of the fan, alarm, and emergency exhaust switching;
The clean laboratory also needs to conduct verification of particles, pressure gradient, and air flow direction synchronously.